QO2201021
AI

The **QO2201021** is a specialized molded case circuit breaker manufactured by **Schneider Electric (Square D)**. It is part of the QO (Quick-Open) product line, known for high reliability in residential and commercial electrical panels.
The specific suffix **1021** indicates that this unit is a **Shunt Trip** circuit breaker.
---
## Technical Specifications
| Feature | Specification |
| :--- | :--- |
| **Product Type** | Miniature Circuit Breaker (MCB) |
| **Poles** | 2-Pole |
| **Current Rating** | 20 Ampere |
| **Voltage Rating** | 120/240 V AC |
| **Interrupting Rating** | 10 kA (10,000 Amps) |
| **Mounting Type** | Plug-On |
| **Special Feature** | 120/208/240 V AC Shunt Trip |
| **Wire Size** | #14 - #8 AWG (Al/Cu) |
---
## Key Components & Electronic Parts
While a standard circuit breaker is primarily mechanical, the **QO2201021** includes an electronic/electromechanical sub-assembly to handle the "Shunt Trip" functionality.
### 1. The Shunt Trip Accessory (The "1021" Component)
The most critical part of this specific model is the internal **Shunt Trip coil**.
* **Function:** This is an electromagnetic coil that allows the breaker to be tripped remotely by an external voltage source (like a fire alarm system or an emergency stop button).
* **Operation:** When the coil receives a 120V signal, it creates a magnetic field that moves a plunger, physically hitting the trip bar and opening the circuit.
### 2. Thermal-Magnetic Mechanism
The breaker uses two methods for standard protection:
* **Bimetallic Strip (Thermal):** Protects against long-term overloads. As current flows, the strip heats up and bends, eventually releasing the trip latch.
* **Electromagnetic Solenoid (Magnetic):** Protects against short circuits. High instantaneous current creates a magnetic force that trips the breaker immediately.
### 3. Visi-Trip™ Indicator
A signature feature of the Square D QO line is the red mechanical indicator. When the breaker trips, a red window appears, allowing for quick visual identification of the fault.
---
## Common Applications
* **Emergency Power Off (EPO):** Used in data centers to shut down power in an emergency.
* **Fire Suppression Systems:** Automatically cuts power to kitchen hoods or machinery when a fire alarm is triggered to prevent the fire from spreading or being fed by electricity.
* **Interlock Systems:** Used in industrial settings where one piece of equipment must be forced off if another fails.
---
- ⤷
How do you wire the shunt trip leads on a QO2201021 breaker?
- ⤷ What is the difference between a shunt trip and an undervoltage release?
- ⤷ Can this breaker be used in a standard residential QO load center?