## 1. Core Technical Specifications
The part number defines its specific electrical characteristics:
| Feature | Specification |
| :--- | :--- |
| **Contact Configuration** | 2 C/O (Double Pole Double Throw - DPDT) |
| **Control Circuit Voltage** | 110 V DC |
| **Rated Operational Current** | 12 A (at 250V AC / 28V DC) |
| **Conventional Enclosed Thermal Current** | 12 A |
| **Shape of Pin** | Flat (Plug-in type) |
| **Status LED** | Included (Indicates coil energization) |
| **Control Type** | Lockable test button |
---
## 2. Component Analysis
The RXM2AB2FD consists of several key electronic and mechanical sections:
### A. The Coil (The Input)
* **Voltage:** 110 V DC.
* **Function:** When 110V DC is applied, the coil creates an electromagnetic field that pulls the armature.
* **Power Consumption:** Average consumption is approximately 0.9 W.
### B. The Contacts (The Output)
* **Material:** Silver Alloy (AgNi). This material provides a good balance between electrical conductivity and resistance to "welding" or oxidation.
* **Switching Capacity:** 3000 VA (AC) / 336 W (DC).
* **Minimum Switching Capacity:** 170 mW at 10 mA, 17 V.
### C. Auxiliary Features
1. **Mechanical Indicator:** A mechanical flag that moves to show if the contacts have switched.
2. **LED Indicator:** A built-in green LED that lights up when the coil is energized, allowing for quick visual troubleshooting.
3. **Test Button:** A manual turquoise button that allows operators to mechanically force the contacts to change state for testing circuits without energizing the coil.
---
## 3. Wiring and Pin Layout
The relay uses a standard pinout for the RXM range, typically mounted on a **ZRX** socket.
```text
Pin Logic:
- Pins 13-14: Coil Connections (+/- for DC)
- Pins 9-12: Common (C)
- Pins 1-4: Normally Closed (NC)
- Pins 5-8: Normally Open (NO)
```
---
## 4. Durability and Environment
* **Mechanical Durability:** 10,000,000 cycles.
* **Electrical Durability:** 100,000 cycles for resistive loads.
* **Operating Temperature:** -40°C to 55°C.
* **IP Degree of Protection:** IP40.
- ⤷