3 / 6 page ![]() MODEL: R30SVF4 R30SVF4 SPECIFICATIONS ES-9023 Rev.3 Page 3/6 https://www.m-system.co.jp/ CONFIGURATOR SOFTWARE SETTING The following parameters can be set with using PC Configurator Software (model: R30CFG) Refer to the users manual for the R30CFG for detailed operation of the software program. ■ CHANNEL INDIVIDUAL SETTING PARAMETER SETTING RANGE DEFAULT SETTING Unused setting CH enabled CH disabled CH enabled Input range -10 – +10 V DC -5 – +5 V DC -1 – +1 V DC 0 – 10 V DC 0 – 5 V DC 1 – 5 V DC 0 – 1 V DC -0.5 – +0.5 V DC -20 – +20 mA DC 4 – 20 mA DC 0 – 20 mA DC -10 – +10 V DC Fine zero adjustment -320.00 – +320.00 (%) 0.00 (%) Fine gain adjustment -3.2000 – +3.2000 1.0000 Scaled range Zero -32 000 – +32 000 0 Scaled range Span -32 000 – +32 000 10 000 ■ CHANNEL BATCH SETTING PARAMETER SETTING RANGE DEFAULT SETTING Averaging number 1, 2, 4, 8, 16, 32, 64, 128, 256 1 Simulate input Normal input Simulated data Normal input |
|
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|