20 / 23 page ![]() (2) UL508A has provisions to raise the rating of power distribution blocks by the use of current-limiting overcurrent protective devices such as current-limiting fuses (i.e. class J, T, RK1, etc.) in the feeder portion of the circuit. (3) If the SCCR rating for a power distribution block, terminal block or multi-lug connector is not established by (1) or (2) above, then the SCCR is the default 10kA per UL508A, Supplement SB, Table SB4.1. For more in depth application material on SCCR see Industrial Control Panel section of publication SPD or Advanced Guide To Understanding Assembly Short-Circuit Current Rating. SCCR for Multi-Lug Connector (Power Distribution Lug) Switch and Circuit Breaker Switches or circuit breakers with multi-lug connectors for conductor terminations serve a very similar wire management function as power distribution blocks. However, it cannot be assumed that when a multi-lug connector is installed on a circuit breaker or switch, that the SCCR of the multi-lug connector is the same as the interrupting rating of the protective device. Multi-lug connectors are covered under UL Standard 486 A/B. Much like a power distribution block, multi-lug connectors are components for distributing tap conductors to power loads and are not an integral part of the overcurrent protective device operation. Therefore, the multi-lug connector must be evaluated in a short-circuit test with the specific overcurrent protective device and listed with a specific combination SCCR. It is important to note, most switches and circuit breakers are not short-circuit tested with multi-lug connectors. If a multi-lug connector on a circuit breaker or switch does not have a combination SCCR with the specific overcurrent protective device used, then it is to be treated in the same manner as an unmarked power distribution block, which means the SCCR is the default 10kA (UL508A, Supplement SB). To repeat, unless the switch or circuit breaker with a multi-lug connector is specifically marked with a short-circuit current rating, the actual short- circuit current rating is 10,000 amperes (or less, if the interrupting rating of the circuit breaker or fuse is less than 10,000 amperes). The use of a listed and tested combination SCCR will ensure that a higher rating is achieved for the product and aid in achieving a higher overall SCCR for the industrial control panel. PDB Spacing Requirements for Equipment: Depending upon the specific application and the standard to which the equipment is being designed, there are certain PDBs that can meet these spacing requirements, some with a high SCCR. The following details the spacing requirements at 600V based upon the equipment standards. Industrial Control Panels (UL508A): UL508A contains three important requirements to consider when applying power distribution blocks. • Spacing of 1˝ through air, 2˝ over surface (301 to 600V) is required when used in a feeder circuit (that’s everything ahead of or on the line side of the final branch circuit overcurrent protective device). • An assumed short-circuit current rating of 10kA for power distribution and terminal blocks not marked with a higher short-circuit current rating, per UL508A Table SB4.1. • Conductor ampacity requirements based on conductor terminal temperature ratings and UL508A conductor ampacities The following details the requirements regarding the use of power distribution blocks in industrial control panels. Use of Power Distribution Blocks in Industrial Control Panel Feeder Circuits (600V & below) • A Listed PDB (UL1953) can be used “as is” since it meets the 2˝ and 1˝ spacing requirements for feeder circuits in UL508A section 10.2 (see Table 10.2) & 28.2.4. • A Recognized Terminal Block (UL1059) can only be used if it meets the spacing requirements in UL508A sections 10.2 (see Table 10.2) & 28.2.1 and it is suitable for field wiring (use Group A, C or D of UL 1059). – Use Group A: Service — including dead-front switch boards, panelboards, service equipment, and the like. – Use Group B: Commercial appliances, including business equipment, electronic data processing equipment, and the like. – Use Group C: Industrial, general. – Use Group D: Industrial, devices having limited ratings. Such as where the load on any single circuit of the terminal block does not exceed 15 amperes at 51 to 150 volts, 10 amperes at 151 to 300 volts, 5 amperes at 301 to 600 volts, or the maximum ampere rating, whichever is less. Listed PDBs have adequate spacing for feeder circuit applications but most recognized terminal blocks don’t have the spacing required for use in feeder circuits Spacing between Spacing between live parts of live parts and UL Standard opposite polarity grounded parts or enclosure @600V 508A Feeder Circuits 508A Branch Circuits 1995 HVAC Through air Over surface @600V @600V 1˝ 2˝ 1˝ 3⁄8˝ 1⁄2˝ 1⁄2˝ 3⁄8˝ 1⁄2˝ 1⁄2˝ Note: Refer to Specific UL standards for complete spacing details. Application Notes 1011 SB-BU09622 Page 20 of 23 Data Sheet 1049 |
|
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |