| Electronic Components Datasheet Search |
|
BPD1002 Datasheet(PDF) 8 Page - Bel Fuse Inc. |
|
|
|||||||||||||||||||||||||||||
BPD1002 Datasheet(HTML) 8 Page - Bel Fuse Inc. |
|
8 / 15 page ![]() BCD.00617 Rev AB,16-Nov-2015 Page 8 of 15 MELCHER The Power Partners. Accessories Data Sheet Backplanes BPD, BPF for T Series Battery Selection When selecting a battery, the following aspects should be considered: 1. Batteries are normally specified at 20°C. Steady operation at higher temperatures will shorten the life time of a battery. For every 10 °C temperature increase the battery lifetime is halved. 2. Worst case considerations with regard to the necessary battery capacity should include operation at the lowest possible temperature and highest possible discharge current, since under such conditions a substantial capacity drop has to be expected. 3. The capacity of a battery deteriorates with time. Therefore decisions on battery capacity should be based upon 20% ageing loss. 4. Consult the battery manufacturer for correct layout of the battery system. Selecting the Right Battery and Back Plane Configuration As mentioned in the T series data sheet the power factor correction at the input of the T unit generates a ripple voltage at the output of twice the input frequency, causing a ripple current into the connected battery. For most battery types the low frequency ripple current should not exceed 5 A per 100 Ah (0.05 C). Some manufacturers (with newer battery technology) specify 10 A per 100 Ah (0.1 C). Excessive ripple current can increase the battery temperature and reduces the battery lifetime. For a single phase system additional output capacitors may be necessary depending upon the selected battery type. Note: With the T units symmetrically connected to a 3-phase (Y) mains supply the low frequency output ripple is virtually zero, only a high frequency ripple and noise of <100 mVAC at the switching frequency of 65.5 kHz remains. System Integration Mains Input Voltage Monitoring The T unit interprets a mains failure as a system error, indi- cated by the red Error LED together with a System Good failure signal. Should a dedicated mains failure identification be required this signal would have to be established externally. Available signals/signal combinations (Please also refer to the T Series data sheet on our website): The T unit provides two open collector signals, System Good and Power Down. The System Good signal monitors the operational function of a single T unit. In case of reduced available output power due to a mains failure, a T unit failure or inhibit, the signal changes from low to high impedance. In systems with battery back-up or with n+1 redundancy the failure of one single unit does not cause a failure of the system as the required output power is still available either from the battery or from the remaining T units. To indicate the status of the whole system, the System Good signals of all 3 units should be connected in series on the back plane. The System Good output can be combined with similar out- puts of other DC-DC converters such as CQ units, integrating the additional information into the overall system status signal. If only the system status of the T unit is to be monitored, Sys In should be wired to Vo–. The Power Down signal monitors the output voltage level of the bus bar system. The threshold levels of the 3 possible signals can be individually adjusted by means of resistors R 13/14...R 33/34 (see: T series data sheet) and be used for: • Save data • Disconnecting the load or part of it • Performing a battery test In systems with battery back-up it may be desirable to extend system operation in case of long term mains failures by disconnecting an uncritical part of the load at a certain bus voltage level, triggered by one of the 3 possible power down signals. The 2 remaining signals can be set to the low battery discharge level to get a redundant signal (wired AND) for finally disconnecting the critical part of the load. Note: The Power Down signal has an enlarged hysteresis of approximately 6 V for T 1740 units and 3.5 V for T 1240 units. The Power Down signal(s) can be combined with the System Good signal to give a wired AND (see T series data sheet). In such cases the resulting alarm only becomes active as a result of a mains failure or a converter failure together with a heavily discharged battery. Dimensioning Example of a Battery Charger System in Single Phase Connection Battery charger system in single phase connection: 230 V, 50 Hz, load: 1 kW, battery back-up: 3 h Battery charger: 3 LT 1740 , n+1 redundant configuration, 1.6 kW Conditions: TA = –10 to 40°C for both, charger and battery |
|
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |